著者
宮本晃男 著
出版者
オーム社
巻号頁・発行日
1953
著者
土江 基夫 宮本 晃男
出版者
The Institute of Electrical Engineers of Japan
雑誌
電気学会論文誌A(基礎・材料・共通部門誌) (ISSN:03854205)
巻号頁・発行日
vol.113, no.1, pp.39-42, 1993-01-20 (Released:2008-07-15)
参考文献数
9
被引用文献数
1

Solubility of copper in insulating oil depends on sulfur contents and component of insulating oil. As increasing of sulfur contents, the solubility of copper becomes large. When being added di-tert-butylparacrezole and benzotriazole into the insulating oil, solubility of copper becomes small. Evolution of combustible gas is proportional to amount of copper in insulating oil, and type of gas pattern due to results of gas analysis in insulating oil depends on chemical component of insulating oil. In the case of low aromatic content oil, hydrocarbon gas evolves preferentially, but in the case of high aromatic content oil, hydrogen gas evolves preferentially. Although degradation of the insulating oil is effected by solution of copper, breakdown voltage of insulating paper is not falling down.