- 著者
-
井村 英昭
吉田 正道
- 出版者
- 一般社団法人日本機械学会
- 雑誌
- 日本機械学會論文集. B編 (ISSN:03875016)
- 巻号頁・発行日
- vol.56, no.532, pp.3816-3820, 1990-12-25
- 被引用文献数
-
4
An experimental study on the heat transfer coefficient and critical heat flux in two-phase double-tube thermosyphons was carried out using water, ethanol and R113 as the working liquids. The same experiment for a single-tube thermosyphon was also performed for comparison. The effects of the top-end shape of inner tubes on the heat transfer coefficient and the critical heat flux were investigated in detail. As a result, it was shown that the heat transfer coefficient was not significantly affected by the difference of the top-end shape, but the critical heat flux was very sensitive to the top-end shape of the inner tubes. For R113, the critical heat flux in the thermosyphon with the inner tube having a T- or flange-shape top-end, was about four times as large as that in the single-tube thermosyphon.