- 著者
-
田辺 新一
長谷部 ヤエ
- 出版者
- 一般社団法人日本建築学会
- 雑誌
- 日本建築学会計画系論文報告集 (ISSN:09108017)
- 巻号頁・発行日
- no.448, pp.1-8, 1993-06-30
- 参考文献数
- 21
- 被引用文献数
-
33
Control principle and evaluation method for thermal environment with the thermal manikin are described in this paper. Under the still air conditions, nude and clothed thermal manikin was exposed to measure skin temperatures and heat loss. Combined heat transfer coefficient for nude conditions were estimated and they were not depended on the surrounding temperatures and its averaged value was 7.9 W/m^2℃. Those at foot and hand were bigger than other parts and thigh and crotch were smaller. The method to calculate PMV from total heat loss was described. Estimation of clo value from heat loss, skin temperature of manikin, and equivalent temperature were discussed here.