A pneumatic nozzle flapper is widely used in pneumatic control systems and is one of the important converting elements. Its transient pressure response has been investigated in several papers, but the case with small time constant has not been reported so far. This paper shows experimentally that the time constant of pneumatic nozzle flapper varies with the direction of pressure step and the position of load capacitor.<br>In the case with steady flow through the load capacitor, the time constant is larger in general than that of side-capacitor, and the time constant of negative pressure response is smaller than that of positive one. These differences are considered to be caused by the heat conduction between air and the capacitor wall.