著者
兎束 哲夫 池戸 昭治 上田 啓二 持永 芳文 船橋 眞男 井手 浩一
出版者
The Institute of Electrical Engineers of Japan
雑誌
電気学会論文誌. B (ISSN:03854213)
巻号頁・発行日
vol.125, no.9, pp.885-892, 2005
被引用文献数
8 7

In AC electric Railway, three-phase voltage is changed into the single-phase circuit of two circuits with the Scott-connected transformer. If it becomes large unbalancing of the load between single-phase circuits, voltage fluctuation becomes large on three-phase side. Then, Railway Static Power Conditioner (RPC) was developed for the purpose of controlling voltage fluctuation on three-phase side. An RPC is comprised of a pair of self-commutated PWM inverters. These inverters connect the main phase and teaser feeding buses, coupled with a DC side capacitor such as a Back-To-Back (BTB) converter. In this way, the two self-commutated inverters can act as a static var compensator (SVC) to compensate for the reactive power and as an active power accommodator from one feeding bus to another.<br>20MVA/60kV RPCs started commercial operation in 2002 at each two substations on the newly extended Tohoku Shinkansen for compensating voltage fluctuation on three-phase side caused by traction loads, absorbing harmonic current. The results of operational testing indicate that an RPC can accommodate single-phase loads such as those of PWM-controlled Shinkansen and thyristor phase-controlled Shinkansen, and handle the exciting rush current of transformers, as well as compensate for harmonics successfully.