著者
林 泰弘 松木 純也 鈴木 良治 武藤 英司
出版者
The Institute of Electrical Engineers of Japan
雑誌
電気学会論文誌. B (ISSN:03854213)
巻号頁・発行日
vol.125, no.9, pp.846-854, 2005
被引用文献数
34 17

Sending voltage profile of distribution feeder is controlled by changing a tap of distribution transformer. In a distribution network with distributed generators, for reasons of effect of reversed flows from them and existence of a great number of sending voltage profile candidates, it is not easy to control sending voltage profile within the acceptable voltage limit. In this paper, in order to determine the optimal sending voltage profile of distribution transformer in a distribution network with distributed generators, the authors propose a new method to determine the optimal sending voltage profile so as to minimize total number of tap position's change per day under constraints of acceptable voltage limit. In the proposed method, after calculating acceptable range of three phase voltage of distribution feeder, the optimal profile of tap position within the calculated acceptable voltage range is determined among these candidates by using reduced ordered binary decision diagram (ROBDD) which is an efficient enumeration algorithm. In order to check the validity of the proposed method, numerical simulations are carried out for a distribution network model with a distributed generator.