雑誌
日本建築学会計画系論文報告集 (ISSN:09108017)
巻号頁・発行日
no.429, pp.17-23, 1991-11-30
被引用文献数
4

To estimate the indoor concentration of NOX by the usage of flue-less type combustion appliances, experimental study was carried out in a laboratory where the ventilation rate, consequently oxygen concentration was controlled. The NO generation rate decreased proportionally with the depression of oxygen concentration to a certain point, K_c, beyond which the decrease rate was much less. N0_2 showed the almost constant generation to K_c, beyond which decreased proportional to oxygen concentration. Though we could not determine K_c with radiant type heaters, the decrease of NO_x emission rate was proportional to oxygen and moderate compared to "fan heater"s.