著者
白崎 圭亮 岡田 有功 佐野 憲一朗 岩月 秀樹
出版者
一般社団法人 電気学会
雑誌
電気学会論文誌B(電力・エネルギー部門誌) (ISSN:03854213)
巻号頁・発行日
vol.138, no.8, pp.651-658, 2018-08-01 (Released:2018-08-01)
参考文献数
11
被引用文献数
3

Flicker may be caused by “frequency feedback method with step injection of reactive power” installed in PCS which is generally used as grid-connected inverter in Japan. Therefore, in this paper, characteristics of the flicker were investigated by experiments with actual PCS in single phase circuit. Furthermore, effective means for suppressing the flicker was considered by taking the cause of occurrence of flicker into account. Moreover, it was clarified the differences among PCSs on flicker using multiple actual PCSs. In conclusion, gain of frequency feedback function should be reduced as one of effective means to avoid flicker.