著者
椎名 健雄 宮島 清富 椙本 一登 松野 秀明
出版者
一般社団法人 電気学会
雑誌
電気学会論文誌B(電力・エネルギー部門誌) (ISSN:03854213)
巻号頁・発行日
vol.142, no.11, pp.568-569, 2022-11-01 (Released:2022-11-01)
参考文献数
6

DC magnetic fields under the Hida-Shinano 200kV DC overhead transmission line were assessed by measurements. The DC magnetic fields observed under the DC overhead transmission line are a superposition of the geomagnetic field and that generated by the DC line current. In this study, the DC magnetic fields generated by the transmission line were obtained by a vector subtraction of the geomagnetic field from the total DC magnetic field. The measured geomagnetic field was 47.1μT and the assessed magnetic fields from the line with a current of 2250A were from 3.8μT to 8.3μT depending on the operating condition of the DC transmission line.