著者
鈴木 道哉 岡 建雄 岡田 圭史 矢野 謙禎
出版者
日本建築学会
雑誌
日本建築学会計画系論文集 (ISSN:13404210)
巻号頁・発行日
vol.60, no.476, pp.37-43, 1995
被引用文献数
16 3

Basic sector classification Input / Output table were applied to analyze the construction, operation and renewal of office buildings to obtain the life cycle energy consumption and carbon dioxide emission. Total energy consumption is approximately 9 GJ per square meter of floor area by construction, 1.2 GJ per square meter per annum for operation and 0.037 GJ per square meter per annum for renewal. Total carbon dioxide emission is approximately 980 kg per square meter of floor area by construction, 90 kg per square meter per annum for operation and 3 kg per square meter per annum for renewal.