著者
高木 雅昭 原 亮一 佐藤 敏之 大山 力
出版者
一般社団法人 電気学会
雑誌
電気学会論文誌B(電力・エネルギー部門誌) (ISSN:03854213)
巻号頁・発行日
vol.125, no.12, pp.1177-1186, 2005 (Released:2006-03-01)
参考文献数
15

It is very effective to enhance the robustness of control over the faults occurred in power system in order to realize stable and reliable power supply. The sliding mode control based on the Variable Structure System (VSS) theory is paid attentions as one of the promising robust control scheme. In the sliding mode control, the structure of the control system is changed across the hyper plane (switching plane) in state space so that the state variables of the system are kept on the hyper plane.This paper proposes a novel control method of generator's excitation system in which the concept of sliding mode control is employed. More specifically, the proposed method switches the reference voltage used in AVR according to the sign of switching function. This paper also discusses the systematic design procedure of the optimal hyper plane. Performance and effectiveness of the proposed control method are investigated through both numerical studies and experimental tests using the single-machine infinite-bus system simulator. Both results show that the proposed control method can damp the transient swing caused by a fault effectively.

言及状況

外部データベース (DOI)

はてなブックマーク (1 users, 1 posts)

"論文 一機無限大母線系統シミュレータを用いた発電機励磁系のVSS制御効果の検討" 電学論B,125巻12号,2005年

Twitter (1 users, 1 posts, 0 favorites)

"論文 一機無限大母線系統シミュレータを用いた発電機励磁系のVSS制御効果の検討" 電学論B,125巻12号,2005年 / “_pdf” https://t.co/iTGHMkmMl1