著者
小林 弘造 北村 規明 田辺 新一 西原 直枝 清田 修 岡 卓史
出版者
公益社団法人 空気調和・衛生工学会
雑誌
空気調和・衛生工学会大会 学術講演論文集 平成17年 (ISSN:18803806)
巻号頁・発行日
pp.2053-2056, 2005-07-25 (Released:2017-08-31)

The field study for 134 days, concerning indoor environment quality and productivity of call-center workers, was conducted. Call data of total 13,169 workers was analyzed. The rate of response to calls was adopted as an index to evaluate the worker performance. Worker performance decreased by 2.1 % when the average indoor air temperature rose at 1.0℃. The possibility of the improving productivity under thermal comfortable environment was suggested.
著者
田辺 新一 中野 淳太 小林 弘造
出版者
日本建築学会
雑誌
日本建築学会計画系論文集 (ISSN:13404210)
巻号頁・発行日
vol.66, no.541, pp.9-16, 2001
被引用文献数
16 12

The 65-Node Thermoregulation-Model was developed, based on Stolwijk model. The model has 16 body parts. Each body part consists of core, muscle, fat and skin. In addition, the model has a central blood compartment. Convective and radiative heat transfer coefficients were derived from the thermal manikin experiments. Under steady state condition, mean skin temperature; skin wet tedness and SET^* agreed well with those by 2 node-model. This model can predict fairly well for. skin temperature distribution under thermal neutrality. Under transient condition, trends of mean skin temperature and evaporative heat loss were similar to the subject experiment by Stolwijk.