- 著者
-
藤原 陽三
絵内 正道
鈴木 憲三
羽山 広文
- 出版者
- 日本建築学会
- 雑誌
- 日本建築学会環境系論文集 (ISSN:13480685)
- 巻号頁・発行日
- vol.73, no.628, pp.767-774, 2008-06-30 (Released:2009-09-30)
- 参考文献数
- 9
- 被引用文献数
-
4
2
In order to search trends in further energy saving in highly insulated and airtight houses in Hokkaido, Japan, an actual-condition investigation on a central-heating system fitted in five such houses, each with different methods of construction, was performed. The results were obtained as follows.:1)The equivalent leakage area value of a steel frame construction was 3.2cm2/m2 that was less than a two-by-four construction(0.33cm2/m2) and a conventional wood construction(1.1-1.7cm2/m2) .It is important to be improved air-tightness of steel frame construction houses by various construction methods. 2) Heat loss coefficient estimated from these experimental results was 0.94 -1.59W/(m2•K). To reduce energy consumption for heating,it will become more important to improve thermal-insulation properties and air tightness.3) The heating-system efficiency obtained from these experimental results was in the range of 72 to 93%. Although the ratio of actual boiler capacity to demanded heat-source capacity extrapolated from actual measurements ranges from two to three times,the effect on system efficiency was less than 10%.However it is necessary to include this 10% in the task of planning a heating system.